• 产品描述
  • Catalog
  • Certificate
  • Drawings
    • Commodity name: N8UE2
    Type
     
    Electrical Parameters
    Rated voltage
    (max.continuousvoltage) L-N/PE
         Uc      275/320/385/420/440V
    Nominal discharge
    Current(8/20)                   L-N/PE
    In  5kA                    8kA     10kA                   20kA  30kA                    40kA
    Max.discharge
    Current(8/20)                   L-N/PE
    Imax 10kA                  5kA 20kA                  40kA 60kA                   80kA
    Max.discharge
    current(10/350)                L-N/PE
    limp /                        / /                           /   /                           /
    Voltage protection
    Level at l.                          L-N/PE
    Up ≤1.0/1.5kV ≤1.2/1.8kV ≤1,5/2,0kV ≤1,5/2,2kV ≤1,8/2,5kV ≤2,0/2,5kV
    Response time   L-N/PE tA  ≤25ns
    Max.backup fuse   25Agl/gG 25Agl/gG 63Agl/gG 125Agl/gG 125Agl/gG 200Agl/gG
    operating temperaturw range g -40℃...+80℃
    Relative humidity The altitude
    The altitude
     

    30%-95%

    <3000m

    30%-95%

    <3000m

    30%-95%

    <3000m

    Cross-section area       1.5mm2 ~25mm2 solid/35mm2 flexible
    Mountng on       35mm DIN rail
    Enclosure material    Thermoplastic,UL94-V0
    Dimension    1P=82×18X60mm
    Leakage current IPE  ≤20μA(DC), ≤300μA( AC)
    Certification    CE(LVD,EMC)
    Type of remote
    signalling contact
       Switching contact
    Switching capacity UN/I  250V/0.1A,125V/0.2A,75V/0.5A
    Cross-sectional area for
    Remote signalling contact
       Max.1.5mm2 soild/flexible
    The use of voltage       Un:220/230V AC
    Execution standard    IEC 61643-1:2011
    Installation      2P, 4P, 1+NPE, 3+NPE
    Packing unit    1 PCS

online message