    • Commodity name: Fault arc switch. 2
    Electrical Specifiction
    Product Standard
    AFDD: IEC/EN 62606; MCB: IEC/EN60898-1
    Line-votage-independent
    Instantaneous 250A(8/20μs)
    Rated voltage Ue
    230V AC;50/60Hz
    Operational voltage range
    170-264V
    Energy class
    3
    Rated breaking capacity
    6kA
    Rated current
    10-63A
    Rated peak withstand voltage UIMP
    4kV(1.2/50μs)
    Arc falut triping Ɵmes aŌ er load current
    Load current
    2.5
    Tripping time(s)
    <1
    5
    <0.5
    10
    <0.25
    16
    <0.15
    32
    <0.12
    40
    <0.12
    Tripping Characteristic
    B,C,D
    Maximum back-up fuse (short circuit)
    100a gL(>10kA)
    Endurance electrical comp.
    4000 switching operations
    mechanical comp.
    20000 switching operations
    Mechanical
    Terminal capacity
    1-25mm²
    Busbar thickness
    0.8-2mm
    Degree of protecƟ on switch
    IP20
    Degree of protecƟ on ,built-in
    IP40
    Tripping temperature
    (-25℃ to+40℃)
    Storage-and transport temperature
    (-35℃to+60℃)
    ProtecƟ on FuncƟ on
    Series connecƟ on arc, Parallel connecƟ on arc,
    landing arc, Overcurrent, Overload

     

  • 2